JENEsys® EDGE™ 534 Controller with N4 (1250 Point Limit and 25 Device Limit)

$8,956.16 To see product price, add this item to your cart. You can always remove it later. What's this?

JENEsys Edge products are available to any certified Niagara integrator or contractor.

NOTE: Unlimited Device Option Is Not Available for this point count

The EDGE 534 Controller, includes Niagara Framework, 512MB RAM, 4GB Flash, one 10/100 Mb Ethernet port, two RS-485 serial ports,  two RJ45 IP ports, a Mini-B USB and a Micro USB connectors.  Standard features include Niagara station with 1250 point Global Capacity & 1250 point Proprietary Driver Capacity (onyxxDriver) and 25 device limit.  Standard drivers include Niagara Network (Fox), BACnet, Modbus, Web and Obix. The JENE-EG534 is designed with a real-time-clock and DIN rail mounting.  Includes Niagara release 4.2.36. Each Module includes 34 IO points: 16 Universal Inputs, 10 Digital Outputs and 8 Analog Outputs.

OR
  • Description
  • Options
  • Terms
  • Deliver the Reliability of Niagara® to the Edge Connect & Access Data—
    Anytime, Anywhere Reduce Engineering Time & Installation Costs Features Specifications

    JENEsys® Edge™ products are a new generation of IoT controllers combining the Niagara Framework® with Lynxspring’s Onyxx® platform. A first-of-its-kind, the JENEsys Edge 534 is a fully programmable Niagara controller with 34 IO built in and expandable IO available, delivering edge connectivity, interoperability, data access and analytics for today's buildings, energy management, machine-to-machine applications and IoT environments. 

    Taking Niagara to the edge with real-time control—the JENEsys Edge 534 utilizes the same familiar ProBuilder/ Workbench software, Niagara programming tools and Fox Protocol.

    Note:  Add to a JENE-EG534, up to 8 additional Onyxx-XM34IO extender modules (at 34 points of IO each) for a maximum of 306 points.

    **This product is intended for those who have the training and tools to utilize Niagara**

    Purpose-built, Lynxspring’s JENEsys Edge 534 delivers edge connectivity, data access and control for today's small to mid-sized facilities, plant control, machine-to-machine and IoT applications that require smart edge technology. 

    The JENEsys Edge 534 combines Niagara and Onyxx, a proven IoT edge hardware platform, enabling facility managers, operators, system integrators and contractors to use a known user interface (ProBuilder/Workbench) to achieve operational efficiencies between multiple systems and/or devices, facility management functions, equipment control and business applications. 

    The bottom line is that the JENEsys Edge 534 licensing is well-suited to take Niagara into smaller or mid-sized and price-sensitive applications. 

    ü  JENEsys = fully programmable Niagara controller

    ·         Fox Protocol

    ·         Same Programming Tools—ProBuilder/Workbench

    ü  34 points of IO on-board and enables an Onyxx Network

    ü  Fast & increased memory capacity

    ü  Small unit footprint (4.5” x 4.25” x 2.25”)

    ü  Real-time Linux OS 

    ü  Powered by Niagara®

    ü  Supports JAVA Web Start

    ü  Standard Niagara drivers—Niagara Network (Fox), BACnet, Modbus, Web & oBIX

    ü  Compatible with many additional 3rd party drivers

    ü  10 Digital Outputs

    ·         Form A contacts, 24V at 0.5 Amp

    ü  8 Analog Outputs

    ·         0-10 Vdc

    ü  16 Universal Inputs

    ·         Type-3 10k ohm thermistors

    ·         Resistance 0-100 K ohms

    ·         0-10 Vdc

    ·         0-20 mA using a 499 ohm resistor

    ·         Pulse input; up to 500Hz

    ü  10/100 Mbps Ethernet (2), RS-485 (2), USB (2)

    ü  Standard RS-485 multi-drop communication bus

    ü  4G eMMC flash memory

    ü  1GHz AM335x ARM Cortex A-8 Processor

    ü  Existing Niagara stations can be added

    ü  24 Vac/dc power input, ideal for equipment control and monitoring applications

    ü  Runs on Onyxx®—an extensible platform

    ü  Leverages global capacity licenses

    ü  35 mm DIN rail or flat panel mounting 

    JENEsys Edge 534 with N4 Data Sheet